Speck Firecell FC II DUO 40-50-1 fire extinguishing system 562.4005.120

    55,379.82 € 55,379.82 € 55379.82 EUR

    55,379.82 €

    Option not available

    Diese Kombination existiert nicht.

    Add to cart

    Delivery rate series: Q up to max. 55 m³/h | Delivery head series: H up to max. 150 m | Media temperature series: t up to max. 20 °C | Operating pressure series: p up to max. 16 bar | Drive voltage: 3~ 400/230 V ± 10 %
    3~ 690/400 V ± 10 % | Drive speed: 2850 min-1


    In the profluid store simply buy online - for larger orders or scale discounts please contact us for an individual offer.
     
    The offer is exclusively for professionals. 

    Speck Feuercell FC II DUO 40-50-1 fire extinguishing system 562.4005.120


    Partnumber :562.4005.120


    Speck fire extinguishing system 562.4005.120 Feuercell FC II DUO 40-50-1

    Drinking water separation stations prevent the medium from flowing back from service water lines connected behind it into the drinking water line and are used in fire extinguishing systems, sprinkler systems, laboratory water systems and in agriculture. The line, as well as the associated pressure boosting system for fire extinguishing purposes, is generally filled with water. The stagnant water here leads to contamination of the drinking water pipe. This water is not of drinking quality and may contain pathogens. It is therefore extremely questionable in terms of hygiene. Fire extinguishing systems must never be used to supply drinking water, because wall hydrant supply systems contain water that corresponds to drinking water category 5 and must therefore be separated from the drinking water network. As a manufacturer of drinking water separation stations for the supply of fire-fighting water, SPECK guarantees hygiene by separating the drinking and service water using a preliminary tank, which we generally have a DVGW certificate for safe connection to W 540 and is also tested by DEKRA. Our systems offer comfort with motorized ball valves, which prevent pressure surges in the lines by opening and closing as required, and can also easily comply with the specifications for flushing according to the latest DIN 1988 Part 600 with flow rates of max. 2 m/sec. In extinguishing water systems according to DIN 14462, the supply line is flushed once a week according to DIN 1988-600, with safety devices according to DIN EN 1717 type AB, with a free outlet and a controlled emergency overflow to protect the drinking water, with the aim of ensuring maximum safety. For this purpose, systems are used that are tailored to the entire system down to the smallest detail, for a long service life of your extinguishing water supply. To control the system, we have developed a simple but well thought-out principle based on decades of experience. All information can easily be called up via the display. By installing standardized branded products as part of the control, it can be easily repaired anywhere in the world. That saves time and money. We guarantee a 100% final test for every drinking water separation station. All products go through a standardized testing process that is documented for our customers. This ensures that the commissioning of Speck drinking water separation stations for extinguishing water supply will be a complete success.

    Application


    Extinguishing water supply, mains disconnection, sprinkling, water supply

    Tech. Details

    Technical details
    Flow rate series Q up to max. 55 m³/h
    Head of series
    H up to max. 150 m
    Media temperature series
    t up to max. 20 °C
    Operating print series
    p up to max. 16 bar
    Funding medium
    Clear liquids chemically affecting the equipment materials and do not attack mechanically.
    Drive Protection
    IP 55
    Drive insulation class
    F
    Drive Voltage
    3~ 400/230 V ± 10 % 3~ 690/400V ± 10%
    Drive speed
    2850 rpm
    Drive frequency
    50 Hz
    Type code
    Feuercell FC II Duo 40-40-2 Feuercell FC: extinguishing water system II (I - without): incl Duo: double pump system 40: pump size 40: number of stages x 10 -2: reduced impeller
    Special versions
    — Extinguishing water systems for larger flow rates and higher operating pressures. — Fire-fighting water systems without a feed tank, type FC I/FC I Duo.
    Rated current (A) 3~ 400V
    32.1
    Weight approx. (kg)
    705
    Pipe connections DNS/DND
    2 x Rp 2/2x DN 80
    Flow rate (m³/h) Average flow rate (m³/h)
    36
    Head at Q H (bar)
    10.4
    Power output P2
    18.5
    Boiler
    N/A
    Max Funding Height
    11,9
    Max. Conveyor stream
    N/A
    Material pump housing
    Stainless steel 1.4301
    Material wheels
    Stainless steel 1.4301
    Material pump shaft
    Stainless steel 1.4305
    Mechanical seal material
    Carbon/SiC/EPDM
    Material fittings
    Copper alloy or cast iron
    Piping material
    Stainless steel 1.4571
    Material base frame
    Stainless steel 1.4301
    Material storage container
    PE
    Material guide vanes
    Stainless steel 1.4301

    Execution



    Fully automatic pressure boosting systems according to DIN 14462 . All systems are wired ready for connection and cpl. piped (on base frame with rubber buffers). All aggregates own a fully automatic pump control, as well as a unpressurized feed tank. The Feuercell FC extinguishing water system Duo is redundant.